Title :
Interruption behaviours with 84/72-kV VCB and GCB
Author :
Tokoyoda, Sho ; Takeda, Takahiro ; Kamei, Kentaro ; Yoshida, Daisuke ; Ito, H.
Author_Institution :
Transm. & Distrib. Syst. Center, Mitsubishi Electr. Corp., Amagasaki, Japan
Abstract :
The interruption behaviours of a high voltage vacuum circuit breaker (VCB) have been investigated in detail [1]-[3]. A VCB has several specific interruption behaviours compared to an SF6 gas circuit breaker (GCB). In particular, a higher thermal interruption capability and a high frequency (HF) re-ignition and HF interruption phenomena might cause switching overvoltage. Interruption behaviours such as the chopping characteristic and HF re-ignition and HF interruption behaviours were measured in this study under the same testing conditions as for several current interruption testing duties using a model VCB and GCB with the same rated voltage of 84/72 kV. The results show that the current chopping level of the VCB is relatively low, so any overvoltage due to current chopping when using a HV-VCB does not significantly influence transmission networks. However, HV-VCB iterates the HF re-ignitions and HF interruptions during the half cycle of inductive current (180-700 A) switching tests and additional large current switching tests. Therefore, HV-VCB may generate steep overvoltages, which may affect the protection relay and secondary equipment operations.
Keywords :
gas insulated switchgear; high-voltage engineering; ignition; overvoltage; relay protection; switchgear testing; transmission networks; vacuum circuit breakers; GCB; HF interruption phenomena; HF reignition; HV-VCB; current 180 A to 700 A; current chopping level; current interruption testing; current switching tests; gas circuit breaker; high frequency reignition; high voltage vacuum circuit breaker; inductive current; interruption behaviours; protection relay; secondary equipment operations; switching overvoltage; thermal interruption capability; transmission networks; voltage 72 kV; voltage 84 kV; Artificial intelligence; Artificial neural networks; Interrupters; Switches;
Conference_Titel :
Electric Power Equipment - Switching Technology (ICEPE-ST), 2013 2nd International Conference on
Conference_Location :
Matsue
DOI :
10.1109/ICEPE-ST.2013.6804324