    Lightning arrester choosing for 10kV side with no load of 220kV main transformer

  • Author

    Qinghao Wang ; Tianshi Wang ; Ying Yang ; Chunzhong Zhao ; Wenguang Zhang ; Yang Su

  • Author_Institution
    Maintenance & Test Dept., Fushun Power Supply Co., Fushun, China
  • fYear
    2011
  • fDate
    16-18 Sept. 2011
  • Firstpage
    1611
  • Lastpage
    1613
  • Abstract
    Through the analyzing to arrester thermal breakdown on 10kV side with no load of 220kV main transformer, the fault direct cause is conformed that because the normal voltage of arrester (YH5WS-17/45) is too low, the arrester get over heat, and then thermal breakdown happens. The right nominal voltage choosing methods for gapless arrester and the possibility of gap zinc oxide arrester application are presented in this paper. The shortcoming of the B-phase direct grounding operating type and a arrester parallel connecting with each phase on 10kV side of transformer is the best protecting method are pointed out.
  • Keywords
    arresters; lightning protection; power transformer protection; B-phase direct grounding operating type; arrester thermal breakdown; gap zinc oxide arrester application; lightning arrester; main transformer; voltage 10 kV; voltage 220 kV; Accidents; Arresters; Capacitance; Capacitors; Grounding; Power transformer insulation; Windings; Zinc Oxide arrester; arrester nominal voltage; capacitance transfer over-voltage; temporary over-voltage; thermal Breakdown;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Control Engineering (ICECE), 2011 International Conference on
  • Conference_Location
    Yichang
  • Print_ISBN
    978-1-4244-8162-0
  • Type

    conf

  • DOI
    10.1109/ICECENG.2011.6057311
  • Filename
    6057311