Lightning arrester choosing for 10kV side with no load of 220kV main transformer
Author
Qinghao Wang ; Tianshi Wang ; Ying Yang ; Chunzhong Zhao ; Wenguang Zhang ; Yang Su
Author_Institution
Maintenance & Test Dept., Fushun Power Supply Co., Fushun, China
fYear
2011
fDate
16-18 Sept. 2011
Firstpage
1611
Lastpage
1613
Abstract
Through the analyzing to arrester thermal breakdown on 10kV side with no load of 220kV main transformer, the fault direct cause is conformed that because the normal voltage of arrester (YH5WS-17/45) is too low, the arrester get over heat, and then thermal breakdown happens. The right nominal voltage choosing methods for gapless arrester and the possibility of gap zinc oxide arrester application are presented in this paper. The shortcoming of the B-phase direct grounding operating type and a arrester parallel connecting with each phase on 10kV side of transformer is the best protecting method are pointed out.
Keywords
arresters; lightning protection; power transformer protection; B-phase direct grounding operating type; arrester thermal breakdown; gap zinc oxide arrester application; lightning arrester; main transformer; voltage 10 kV; voltage 220 kV; Accidents; Arresters; Capacitance; Capacitors; Grounding; Power transformer insulation; Windings; Zinc Oxide arrester; arrester nominal voltage; capacitance transfer over-voltage; temporary over-voltage; thermal Breakdown;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Control Engineering (ICECE), 2011 International Conference on
Conference_Location
Yichang
Print_ISBN
978-1-4244-8162-0
Type
conf
DOI
10.1109/ICECENG.2011.6057311
Filename
6057311
Link To Document