• DocumentCode
    2004353
  • Title

    Ampacity of cables in solid bottom trays with and without covers

  • Author

    Rebbapragada, R.V. ; O´Neill, D. ; Zuzovsky, M. ; Weronick, R.

  • Author_Institution
    Raytheon Nucl. Inc., Princeton, NJ, USA
  • Volume
    3
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    1704
  • Abstract
    Nuclear Power Generating Stations utilize cable trays to route cables that are part of safety related systems. While these trays are predominantly ladder type (ventilated), there are several instances where solid bottom trays, with or without covers, are also applied. The guidance, to determine the ampacity of cables installed in ventilated or solid bottom trays without covers is given in Section 318-11 of the National Electric Code. Guidance to determine the ampacity of cables installed in ventilated or solid bottom trays with covers is also given under “Provision 2” of this same article which states, “a derating of not over 95% of the allowable ampacities for uncovered trays recommended”. However, adequate justification to this derating factor is not presented. Due to lack of any industry guidance to determine ampacity of cables in solid bottom trays (with or without covers) the authors performed the required analyses. A summary of the analytical techniques used and the derating factors applicable to the solid bottom trays are presented
  • Keywords
    fission reactor safety; power cables; safety systems; Nuclear Power Generating Stations; ampacity; cable trays; safety related systems; solid bottom trays; Cables; Equations; Heat transfer; National electric code; Nuclear power generation; Power generation; Predictive models; Safety; Solids; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Nuclear Science Symposium, 1999. Conference Record. 1999 IEEE
  • Conference_Location
    Seattle, WA
  • ISSN
    1082-3654
  • Print_ISBN
    0-7803-5696-9
  • Type

    conf

  • DOI
    10.1109/NSSMIC.1999.842917
  • Filename
    842917