DocumentCode
2004353
Title
Ampacity of cables in solid bottom trays with and without covers
Author
Rebbapragada, R.V. ; O´Neill, D. ; Zuzovsky, M. ; Weronick, R.
Author_Institution
Raytheon Nucl. Inc., Princeton, NJ, USA
Volume
3
fYear
1999
fDate
1999
Firstpage
1704
Abstract
Nuclear Power Generating Stations utilize cable trays to route cables that are part of safety related systems. While these trays are predominantly ladder type (ventilated), there are several instances where solid bottom trays, with or without covers, are also applied. The guidance, to determine the ampacity of cables installed in ventilated or solid bottom trays without covers is given in Section 318-11 of the National Electric Code. Guidance to determine the ampacity of cables installed in ventilated or solid bottom trays with covers is also given under “Provision 2” of this same article which states, “a derating of not over 95% of the allowable ampacities for uncovered trays recommended”. However, adequate justification to this derating factor is not presented. Due to lack of any industry guidance to determine ampacity of cables in solid bottom trays (with or without covers) the authors performed the required analyses. A summary of the analytical techniques used and the derating factors applicable to the solid bottom trays are presented
Keywords
fission reactor safety; power cables; safety systems; Nuclear Power Generating Stations; ampacity; cable trays; safety related systems; solid bottom trays; Cables; Equations; Heat transfer; National electric code; Nuclear power generation; Power generation; Predictive models; Safety; Solids; Temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Nuclear Science Symposium, 1999. Conference Record. 1999 IEEE
Conference_Location
Seattle, WA
ISSN
1082-3654
Print_ISBN
0-7803-5696-9
Type
conf
DOI
10.1109/NSSMIC.1999.842917
Filename
842917
Link To Document