• DocumentCode
    2032018
  • Title

    Surge withstand performance of MCB used as backup overcurrent protection of SPD

  • Author

    Zhou, Qibin ; Zhao, Yang ; Sun, Wei

  • Author_Institution
    Lightning Protective Device Testing Center, Shanghai Lightning Protection Center, Shanghai, China
  • fYear
    2012
  • fDate
    2-7 Sept. 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presented an experimental study on the surge withstand performance of MCBs (Miniature Circuit Breaker) which are tendentiously used as backup overcurrent protection of SPDs. The maximum and 15-shots withstand capability of MCBs for 10/350μs and 8/20μs surges were found through test and compared with those of fuses. Meanwhile the surge withstand capability of the MCBs with various a.c. switching capability and characteristic curves were compared. Then the damaged and triggering mechanism of MCB under surges was investigated. The residual voltage of MCB under 8/20μs surges and the surge withstand capability of MCCB (Moulded Case Circuit Breaker) under 10/350μs surges were discussed finally.
  • Keywords
    circuit breakers; overcurrent protection; surge protection; MCB damaged mechanism; MCB residual voltage; MCB triggering mechanism; MCCB surge withstand capability; SPD backup overcurrent protection; miniature circuit breaker; moulded case circuit breaker surge withstand capability; Fuses; Generators; Sun; Surge protection; Surges; Switches; MCB; SPD; coordination; surge withstand capability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Lightning Protection (ICLP), 2012 International Conference on
  • Conference_Location
    Vienna
  • Print_ISBN
    978-1-4673-1898-3
  • Electronic_ISBN
    978-1-4673-1896-9
  • Type

    conf

  • DOI
    10.1109/ICLP.2012.6344302
  • Filename
    6344302