DocumentCode :
2044557
Title :
Non-destructive diagnostic testing of service aged MV XLPE cables
Author :
Hvidsten, Sverre ; Faremo, Hallvard ; Benjaminsen, Jan Tore ; Ildstad, Erling
Author_Institution :
SINTEF Energy Res., Norway
fYear :
2000
fDate :
2000
Firstpage :
137
Lastpage :
140
Abstract :
In this paper, results from diagnostic measurements performed on service aged 12 and 24 kV XLPE cables are reported. The main purpose of this work has been to test two non-destructive diagnostic test methods based upon measurements of return voltage and depolarisation current. The actual condition of the cables was determined by laboratory AC breakdown tests and water tree examinations. Both methods detected bad cables containing high density of long vented water trees. However, additional measurements of polarisation currents are needed to detect water trees bridging the insulation. The evaluation criteria need to be further developed, in order to reliably assess the condition of cables with very few but long vented water trees
Keywords :
XLPE insulation; ageing; dielectric depolarisation; dielectric loss measurement; electric current measurement; insulation testing; power cable insulation; trees (electrical); voltage measurement; 12 kV; 24 kV; AC breakdown tests; condition assessment; depolarisation current measurement; dielectric response; long vented water trees; nondestructive diagnostic testing; return voltage measurement; service aged MV XLPE cables; water tree examination; Aging; Cables; Current measurement; Electric breakdown; Laboratories; Nondestructive testing; Performance evaluation; Polarization; Trees - insulation; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
Conference_Location :
Anaheim, CA
ISSN :
1089-084X
Print_ISBN :
0-7803-5931-3
Type :
conf
DOI :
10.1109/ELINSL.2000.845476
Filename :
845476
Link To Document :