DocumentCode
2103199
Title
The new method of monitoring DC system insulation on-line
Author
Zhao, Chengyong ; Jia, Xiufang ; Zhifang Hao
Author_Institution
Electr. Power Eng. Dept., North China Electr. Power Univ., Baoding, China
Volume
1
fYear
2001
fDate
2001
Firstpage
688
Abstract
A novel method of detecting an earth fault on a DC system is by the principle of magnetic modulation is proposed in the paper. The method can determine not only individual leakage loop but also the special case of both positive bus wire and negative bus wire insulation fault simultaneously by putting a resistance into the DC bus. Finally, the good results are shown in the paper. The performance of the detecting apparatus is good in the selection loop and strong in anti-interference, as well as it not showing any effect on the DC system through the experiment
Keywords
electric current measurement; insulation testing; leakage currents; magnetic leakage; power system faults; DC system insulation; anti-interference; earth fault detection; leakage current detection; leakage loop; magnetic modulation; negative bus wire insulation fault; on-line monitoring; positive bus wire insulation fault; power plants; substations; Circuit faults; Earth; Electrical fault detection; Frequency conversion; Insulation; Leak detection; Magnetic flux; Magnetic modulators; Monitoring; Voltage;