• DocumentCode
    2145849
  • Title

    The residual resistivity in soil ionization region around grounding system for different experimental results

  • Author

    Liu, Yaqing ; Theethayi, Nelson ; Gonzalez, Raul M. ; Thottappillil, Rajeev

  • Author_Institution
    Div. for Electr. & Lightning Res., Uppsala Univ., Sweden
  • Volume
    2
  • fYear
    2003
  • fDate
    18-22 Aug. 2003
  • Firstpage
    794
  • Abstract
    The residual soil resistivity at peak of injection current with lightning current wave shape in soil ionization region around the grounding system is analyzed based on different experimental results in the literature by E.E. Oettle (1988), P.L. Bellaschi et al. (1942) and A.C. Liew and M. Darveniza (1974) and the recent experimental results in the high voltage laboratory at Uppsala University. The results show that the residual resistivity in soil ionization region is changing largely versus different soil resistivity ranging from 50 Ωm to 827 Ωm. Combining all the data, the geometric mean of the residual soil resistivity in ionization region is approximately 7% of the original soil resistivity. This value of 7% can be used in modeling of the transient behavior of grounding system under the lightning strike including non-linear soil ionization phenomenon.
  • Keywords
    earthing; electrical resistivity; ionisation; lightning; power systems; soil; grounding system; injection current; lightning current wave shape; lightning strike; nonlinear soil ionization phenomenon; residual resistivity; soil ionization region; soil resistivity; transient behavior; Conductivity; Conductors; Electrodes; Grounding; Ionization; Laboratories; Lightning; Shape; Soil; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetic Compatibility, 2003 IEEE International Symposium on
  • Print_ISBN
    0-7803-7835-0
  • Type

    conf

  • DOI
    10.1109/ISEMC.2003.1236709
  • Filename
    1236709