Lightning flashover rates of overhead distribution lines applying volt time curve from testing and IEEE Std.1410-2004
Author
Thanasaksiri, T.
Author_Institution
Dept. of Electr. Eng., ChiangMai Univ., Chiangmai, Thailand
fYear
2011
fDate
17-19 May 2011
Firstpage
661
Lastpage
664
Abstract
This paper calculates the lightning flashover rates of 22 kV overhead distribution line. In order to calculate the backflashover rate (BFOR), the performance of line which related to the insulator backflashover has been modeled and analyzed using Electromagnetic Transient Program (EMTP). The shielding failure flashover rate (SFFOR) and induced voltage flashover rate (IVFOR) have been calculated follow equations given in IEEE std 1410-2004. Finally the total numbers of flashovers of line have been determined. The lightning flashovers rates of BFOR, SFFOR and IVFOR have also been compared with the data taken from the line outages recorder. From the system being studied shown that, the total numbers of flashovers from simulation and calculation is closed to the data from the line outage recorder.
Keywords
EMTP; IEEE standards; flashover; lightning; power distribution lines; power overhead lines; EMTP; Electromagnetic Transient Program; IEEE Std. 1410-2004; backflashover rate; induced voltage flashover rate; insulator backflashover; lightning flashover rates; line outages recorder; overhead distribution lines; shielding failure flashover rate; volt time curve; voltage 22 V; Capacitors; EMTP; Equations; Flashover; Lightning; Mathematical model; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2011 8th International Conference on
Conference_Location
Khon Kaen
Print_ISBN
978-1-4577-0425-3
Type
conf
DOI
10.1109/ECTICON.2011.5947926
Filename
5947926
Link To Document