• DocumentCode
    2188262
  • Title

    Lightning flashover rates of overhead distribution lines applying volt time curve from testing and IEEE Std.1410-2004

  • Author

    Thanasaksiri, T.

  • Author_Institution
    Dept. of Electr. Eng., ChiangMai Univ., Chiangmai, Thailand
  • fYear
    2011
  • fDate
    17-19 May 2011
  • Firstpage
    661
  • Lastpage
    664
  • Abstract
    This paper calculates the lightning flashover rates of 22 kV overhead distribution line. In order to calculate the backflashover rate (BFOR), the performance of line which related to the insulator backflashover has been modeled and analyzed using Electromagnetic Transient Program (EMTP). The shielding failure flashover rate (SFFOR) and induced voltage flashover rate (IVFOR) have been calculated follow equations given in IEEE std 1410-2004. Finally the total numbers of flashovers of line have been determined. The lightning flashovers rates of BFOR, SFFOR and IVFOR have also been compared with the data taken from the line outages recorder. From the system being studied shown that, the total numbers of flashovers from simulation and calculation is closed to the data from the line outage recorder.
  • Keywords
    EMTP; IEEE standards; flashover; lightning; power distribution lines; power overhead lines; EMTP; Electromagnetic Transient Program; IEEE Std. 1410-2004; backflashover rate; induced voltage flashover rate; insulator backflashover; lightning flashover rates; line outages recorder; overhead distribution lines; shielding failure flashover rate; volt time curve; voltage 22 V; Capacitors; EMTP; Equations; Flashover; Lightning; Mathematical model; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2011 8th International Conference on
  • Conference_Location
    Khon Kaen
  • Print_ISBN
    978-1-4577-0425-3
  • Type

    conf

  • DOI
    10.1109/ECTICON.2011.5947926
  • Filename
    5947926