• DocumentCode
    2199581
  • Title

    Improved insert geometry for reducing tank wall

  • Author

    Olivares, J.C. ; Escarela-Perez, R. ; Kulkarni, S.V. ; de Leon, Francisco ; Melgoza, E. ; Hernandez, Oscar ; Olivares, J.

  • fYear
    2004
  • fDate
    6-10 June 2004
  • Abstract
    Summary form only given. This work presents a numerical analysis of losses generated in the tank wall surrounding the high-current bushings of pad-mounted transformers using a three-dimensional finite-element approach. Two cases are analyzed to study the impact of inserting small plates of different geometry (located near the high-current phases) on the reduction of tank losses. Significant reductions in stray losses occurring in the tank wall are obtained with plate inserts of low-cost. With the "T" configuration proposed in This work we reduce the tank wall losses by a factor of 1/21 at rated current when compared with the case of tank wall without the stainless steel plate. A three-dimensional time-harmonic finite-element model is used to determine the losses in the tank wall. Two load loss tests were carried out on experimental transformers to validate the simulations and effectiveness of the low-cost inserts.
  • Keywords
    bushings; finite element analysis; losses; power transformers; tanks (containers); T configuration; harmonic finite-element model; high-current bushings; load loss test; numerical analysis; pad-mounted transformers; stray losses; tank losses; tank wall; variant geometry plates; Finite element methods; Geometry; Insulators; Numerical analysis; Steel; Testing; Transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2004. IEEE
  • Conference_Location
    Denver, CO
  • Print_ISBN
    0-7803-8465-2
  • Type

    conf

  • DOI
    10.1109/PES.2004.1373099
  • Filename
    1373099