DocumentCode :
2212046
Title :
Diagnostics and Prognostics of Electric Cables in Nuclear Power Plants via Joint Time-Frequency Domain Reflectometry
Author :
Wang, Jingjiang ; Crapse, Philip ; Shin, Yong-June ; Dougal, Roger
Author_Institution :
Dept. of Electr. Eng., Univ. of South Carolina, Columbia, SC
fYear :
2008
fDate :
9-12 June 2008
Firstpage :
24
Lastpage :
27
Abstract :
Defective cables in the electric power systems of nuclear power plants can cause a component to fail, resulting in potential safety concerns. Due to this problem, a non-destructive, non-intrusive condition assessment technique is highly desirable. Joint time-frequency domain reflectometry (JTFDR) is proposed and verified to be effective for cross-linked polyethylene (XLPE) cable, which serves critical instrumentation and control operations in nuclear power plants. The experimental results demonstrate and verify the ability of JTFDR to effectively detect and locate incipient defects with high accuracy and to monitor the aging process of the cables to predict both future defects and the remaining service life of the cables.
Keywords :
XLPE insulation; nondestructive testing; nuclear power stations; power cable testing; remaining life assessment; time-domain reflectometry; cross-linked polyethylene cables; electric cables; joint time-frequency domain reflectometry; nondestructive condition assessment; nuclear power plants; remaining service life assessment; Aging; Cables; Frequency domain analysis; Monitoring; Power generation; Reflectometry; Testing; Time domain analysis; Time frequency analysis; Wire;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
Conference_Location :
Vancouver, BC
ISSN :
1089-084X
Print_ISBN :
978-1-4244-2091-9
Electronic_ISBN :
1089-084X
Type :
conf
DOI :
10.1109/ELINSL.2008.4570268
Filename :
4570268
Link To Document :
بازگشت