Abstract :
This paper shows a complementary study aiming at verifying the influence of the weather conditions on the effectiveness of a previous set of techniques applied to define the operational condition of porcelain pin insulators installed in medium voltage distribution lines. The research method, as discussed in a previous paper [1], deals basically with a preliminary rough inspection with an electromagnetic noises detector and a final close inspection with an ultrasonic noises detector. During the last inspection the temperature, the wind speed and the relative humidity of the air were also recorded to populate a data base with the insulators main data. Once detected a single noisy insulator all insulators installed in the inspected pole were removed and substituted by equivalent post insulators. These insulators were further classified, tested and a comparison of field and laboratory results was used to verify the influence of the weather conditions on the noise level that defines the boundary limit of damaged & no - damaged insulators. The laboratory tests were carried out at the High-Voltage Laboratory of Federal University of Itajuba.
Keywords :
inspection; insulators; poles and towers; power distribution lines; distribution medium voltage lines; electromagnetic noises detector; pole inspection; porcelain pin insulators; ultrasonic noises detector; Detectors; Electromagnetic interference; Humidity; Inspection; Insulation; Laboratories; Medium voltage; Porcelain; Temperature; Wind speed;
Conference_Titel :
Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
Conference_Location :
Vancouver, BC
Print_ISBN :
978-1-4244-2091-9
Electronic_ISBN :
1089-084X
DOI :
10.1109/ELINSL.2008.4570387