• DocumentCode
    2289616
  • Title

    Outdoor polymeric insulators long-term exposed to HVDC

  • Author

    Vlastos, A.E.

  • fYear
    1996
  • fDate
    15-20 Sep 1996
  • Firstpage
    135
  • Lastpage
    142
  • Abstract
    Field experience from outdoor polymeric insulators exposed to HVDC under natural contamination conditions is presented. This paper summarizes the peak leakage current statistics, the hydrophobicity and the surface material conditions studied by electron spectroscopy for chemical analysis (ESCA) and attenuated total reflection Fourier transform infrared (ATR-FTIR) spectroscopy. The results show a strong interrelation between the surface conditions and the performance with respect to leakage currents. Moreover, the results show that the surface conditions and the performance of the insulators exposed to HVDC are rather similar to those of the insulators exposed to HVAC
  • Keywords
    Fourier transform spectroscopy; HVDC power transmission; chemical analysis; electron spectroscopy; infrared spectroscopy; insulator testing; leakage currents; polymer insulators; ATR-FTIR; ESCA; HVDC; attenuated total reflection Fourier transform infrared spectroscopy; electron spectroscopy for chemical analysis; hydrophobicity; natural contamination conditions; outdoor polymeric insulators; peak leakage current statistics; surface conditions; surface material conditions; Chemical analysis; Electrons; HVDC transmission; Infrared spectra; Leakage current; Plastic insulation; Polymers; Spectroscopy; Statistical analysis; Surface contamination;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
  • Conference_Location
    Los Angeles, CA
  • Print_ISBN
    0-7803-3522-8
  • Type

    conf

  • DOI
    10.1109/TDC.1996.545926
  • Filename
    545926