Abstract :
This work presents results of a comparative study conducted on breakdown voltage measurements in a glass insulators string containing several units with broken glass part. String with 16 insulator units were tested simulating a transmission line of 230 kV. Two arrangements have been adopted: (i) seven good insulators and nine broken units and, (ii) six good insulators and ten broken units. The electrical breakdown voltage measurements have been carried out in dry and without pollution, in five different configurations. The experimental works have been conducted in industrial frequency and with switching impulse with positive and negative polarities. As a result, depend on the distribution and localization of the good insulators in the chain, the breakdown voltage values of the chain with six good insulators was higher than the chain with seven good insulators. A string with six good insulators in configuration #4 showed higher value of the electrical breakdown voltage than a string with seven good insulators in configurations #1 and #2.
Keywords :
electric breakdown; glass; insulator testing; power transmission lines; voltage measurement; electrical breakdown voltage measurement; glass insulator string testing; industrial frequency; transmission line; Breakdown voltage; Dielectrics and electrical insulation; Electric variables measurement; Environmentally friendly manufacturing techniques; Glass; Industrial pollution; Insulator testing; Pollution measurement; Transmission line measurements; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
IEEE International Power Modulators and High Voltage Conference, Proceedings of the 2008
Conference_Location :
Las Vegas, NE
Print_ISBN :
978-1-4244-1534-2
Electronic_ISBN :
978-1-4244-1535-9
Type :
conf
DOI :
10.1109/IPMC.2008.4743639
Filename :
4743639
Link To Document :
بازگشت