• DocumentCode
    2317569
  • Title

    Change in pattern of void-type PD with ageing

  • Author

    Guo, D. ; Hepburn, D.M. ; Nesbitt, A. ; Zhou, C.

  • Author_Institution
    Sch. of Eng., Cardiff Univ., Cardiff
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    109
  • Lastpage
    112
  • Abstract
    The measurement and assessment of partial discharge (PD) activity is used both for condition assessment of high voltage plant (by operators) and for quality control (by manufacturers). Except for the online circumstances, the measurement usually lasts for a short period of time while higher than working stress is applied. The resulting pattern of discharge data, when compared with a knowledge base of PD patterns of different types of defects is a crucial factor in diagnosing the condition of the insulation system in the plant.
  • Keywords
    partial discharges; condition assessment; plant insulation system; quality control; void-type partial discharge; Aging; Condition monitoring; Ear; Epoxy resins; Manufacturing; Mathematical model; Partial discharge measurement; Partial discharges; Phase measurement; Stress; φ-q-n patterns; Ageing; Mechanisms; Natural void in resin; Partial discharge;