• DocumentCode
    2321328
  • Title

    Partial discharge weak spots localization in the stator insulation of running turbo generators

  • Author

    Van Breen, Harry J. ; Gulski, Edward ; Smit, Johan J.

  • Author_Institution
    HV Technol. & Manage., Delft Univ. of Technol., Netherlands
  • fYear
    2003
  • fDate
    23-25 Sept. 2003
  • Firstpage
    43
  • Lastpage
    46
  • Abstract
    One of the best symptoms for the presence of defects in the HV insulation system is the detection of partial discharges (PD). Weak spots may be found by evaluating the PD repetition rate over the entire insulation system. If a severe degradation system is active, it will show a much higher PD repetition rate compared to the non-affected part of the insulation system. A method is introduced, which uses the propagation of the pulses through the stator core to localize partial discharges. With the knowledge of the exact spot at which each PD occurs it is possible to determine the PD repetition rate of PD occurrences in the entire stator. Weak spot localization can then be readily identified and localized by their enhanced repetition rate.
  • Keywords
    fault location; insulation testing; machine insulation; partial discharge measurement; stators; turbogenerators; HV insulation system; PD repetition rate; degradation system; partial discharge detection; partial discharge weak spots localization; pulse propagation; stator core; stator insulation; turbogenerators; Bars; Calibration; Coils; Degradation; Insulation; Partial discharges; Power transformers; Stator cores; Turbogenerators; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Technology Conference, 2003. Proceedings
  • ISSN
    0362-2479
  • Print_ISBN
    0-7803-7935-7
  • Type

    conf

  • DOI
    10.1109/EICEMC.2003.1247851
  • Filename
    1247851