Title :
Adaptive out-of-step relay with phasor measurement
Author :
Centeno, V. ; Phadke, A.G. ; Edris, A.
Abstract :
This paper presents the experiences in the development, implementation, and testing of a phasor based adaptive out-of-step relay system installed on the Florida-Georgia intertie. Adaptive characteristics seek to make the relay more attuned to the prevailing power system conditions by adjusting the relay parameters as system conditions change. This work began as a theoretical examination of the application of phasor measurement and adaptive relaying concepts to the simplest stability application. The paper describes the implementation and testing of an adaptive out-of-step relay system, based on phasor measurement and the concepts of equal area criterion applied to an intertie that can be modeled as a two machine system. The paper also includes the major events observed and the results obtained by the relay system over the one year test period
Conference_Titel :
Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
Conference_Location :
Nottingham
Print_ISBN :
0-85296-672-5
DOI :
10.1049/cp:19970065