DocumentCode :
2351527
Title :
Adaptive out-of-step relay with phasor measurement
Author :
Centeno, V. ; Phadke, A.G. ; Edris, A.
fYear :
1997
fDate :
25-27 Mar 1997
Firstpage :
210
Lastpage :
213
Abstract :
This paper presents the experiences in the development, implementation, and testing of a phasor based adaptive out-of-step relay system installed on the Florida-Georgia intertie. Adaptive characteristics seek to make the relay more attuned to the prevailing power system conditions by adjusting the relay parameters as system conditions change. This work began as a theoretical examination of the application of phasor measurement and adaptive relaying concepts to the simplest stability application. The paper describes the implementation and testing of an adaptive out-of-step relay system, based on phasor measurement and the concepts of equal area criterion applied to an intertie that can be modeled as a two machine system. The paper also includes the major events observed and the results obtained by the relay system over the one year test period
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
Conference_Location :
Nottingham
ISSN :
0537-9989
Print_ISBN :
0-85296-672-5
Type :
conf
DOI :
10.1049/cp:19970065
Filename :
608182
Link To Document :
بازگشت