Abstract
In power sysem protection autoreclose schemes, the ability to adapt the dead time allows the mean time to reclosure to be reduced whilst allowing a greater number of successful reclosures. In this respect, adaptive single pole autoreclose (ADSPAR) offers many advantages such as increased rate of successful reclosure, improved stability and a reduction in system and equipment shock for a permanent fault. This paper describes how the ADSPAR technique exhibits clear benefits over conventional SPAR only techniques. The possibility of adapting SPAR introduces a range of new possibilities. It is useful to redefine the ideal response to transmission line faults and thus examine the priorities of electric utilities. Comparisons are made with conventional single shot schemes; however the advantages of inclusion of ADSPAR into a two- or multi-shot scheme is clear
Keywords
power overhead lines; ADSPAR technique; HV overhead lines; adaptive autoreclose relay; adaptive single pole autoreclose; dead time; electric utilities; mean time to reclosure; operating experience; power sysem protection scheme; stability; transmission line faults;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
Conference_Location
Nottingham
ISSN
0537-9989
Print_ISBN
0-85296-672-5
Type
conf
DOI
10.1049/cp:19970103
Filename
608228
Link To Document