• DocumentCode
    2356971
  • Title

    On-site experience of an adaptive autoreclose relay for HV overhead lines

  • Author

    Gardiner, I.P. ; Ramsden, J.

  • Author_Institution
    Reyrolle Protection, UK
  • fYear
    1997
  • fDate
    25-27 Mar 1997
  • Firstpage
    377
  • Lastpage
    380
  • Abstract
    In power sysem protection autoreclose schemes, the ability to adapt the dead time allows the mean time to reclosure to be reduced whilst allowing a greater number of successful reclosures. In this respect, adaptive single pole autoreclose (ADSPAR) offers many advantages such as increased rate of successful reclosure, improved stability and a reduction in system and equipment shock for a permanent fault. This paper describes how the ADSPAR technique exhibits clear benefits over conventional SPAR only techniques. The possibility of adapting SPAR introduces a range of new possibilities. It is useful to redefine the ideal response to transmission line faults and thus examine the priorities of electric utilities. Comparisons are made with conventional single shot schemes; however the advantages of inclusion of ADSPAR into a two- or multi-shot scheme is clear
  • Keywords
    power overhead lines; ADSPAR technique; HV overhead lines; adaptive autoreclose relay; adaptive single pole autoreclose; dead time; electric utilities; mean time to reclosure; operating experience; power sysem protection scheme; stability; transmission line faults;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, Sixth International Conference on (Conf. Publ. No. 434)
  • Conference_Location
    Nottingham
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-672-5
  • Type

    conf

  • DOI
    10.1049/cp:19970103
  • Filename
    608228