Title :
Expression of Rate of Rise of Recovery Voltage across a Circuit Breaker with Fault Current Limiter in Bus-Tie Location
Author :
Desrosiers, Paul Audin ; Calixte, Evenson ; Pierre, Lein S Maillart
Author_Institution :
Quisqueya Univ., Port-au-Prince
fDate :
Sept. 30 2007-Oct. 2 2007
Abstract :
The present paper examines the mathematical expression of the rate of rise of recovery voltage (rrrv) across a circuit breaker as a function of the fault current, the limiting inductance and the circuit parameters when a fault occurs near the terminals of the circuit breaker. The fault current limiter (FCL), composed of an inductance, was assumed to be connected at the bus-tie position. This work provides a mathematical expression of the relationship between the rrrv and the limited current that can be used to find out the dependence of the breaking duty upon the circuit parameters. A small increase in the limiting inductance can reduce significantly the rate of rise of the transient recovery voltage, thus resulting in favorable breaking conditions.
Keywords :
circuit breakers; fault current limiters; bus-tie location; bus-tie position; circuit breaker; fault current limiter; rate of rise of recovery voltage; Circuit breakers; Circuit faults; Fault current limiters; Fault currents; Impedance; Power quality; Power system reliability; Power system transients; Resistors; Voltage; Rate of rise of recovery voltage; breaking condition; bus-tie location; circuit breaker; fault current limiter;
Conference_Titel :
Power Symposium, 2007. NAPS '07. 39th North American
Conference_Location :
Las Cruces, NM
Print_ISBN :
978-1-4244-1726-1
Electronic_ISBN :
978-1-4244-1726-1
DOI :
10.1109/NAPS.2007.4402287