Title :
Influence of smoothing reacteor arrangement on transients of converter station for ±500kV double-circuit HVDC system
Author :
Dong, Manling ; Xie, Shijun ; Zhang, Dandan ; He, Hengxing ; Bao, Minghui ; He, Junjia ; Huang, Ying ; Li, Xiaolin ; Cai, Zongyuan
Author_Institution :
Coll. of Electr. & Electron. Eng., Huazhong Univ. of Sci. & Technol., Wuhan, China
Abstract :
For HVDC transmission system, the smoothing reactor has two structural types; oil-immersed core reactor and air-core reactor. The former needs to concentrate installed on DC-line, and the latter can be arranged flexibly on both pole line and neutral line. According to the different arrangements of smoothing reactors, the system steady-state performance and over-voltage of converter station have some difference. In this paper, the influence of different smoothing reactor arrangements on the system steady-state performance and converter station over-voltage performance of Xiluodu-Guangdong ± 500kV double-circuit HVDC project is analyzed by using ATP/EMTP. A reasonable arrangement of smoothing reactor is proposed, which aims at both maintaining reliability and reducing costs.
Keywords :
AC-DC power convertors; HVDC power transmission; overvoltage protection; power system transient stability; reactors (electric); ATP/EMTP; DC-line; HVDC transmission system; Xiluodu-Guangdong; air-core reactor; converter station over-voltage performance; double-circuit HVDC system; neutral line; oil-immersed core reactor; pole line; smoothing reactor arrangement; system steady-state performance; arrangement methods of smoothing reactor; insulation coordination; overvoltage; smoothing reactor;
Conference_Titel :
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location :
Minneapolis, MN
Print_ISBN :
978-1-4244-6549-1
Electronic_ISBN :
1944-9925
DOI :
10.1109/PES.2010.5589913