• DocumentCode
    2394030
  • Title

    Single-phase ups system with series-parallel filtering capabilities

  • Author

    Barriviera, Rodrigo ; Silva, Sergio A Oliveira da ; Kaster, Maurício ; Modesto, Rodrigo Augusto ; Goedtel, Alessandro

  • Author_Institution
    Fed. Inst. of Parana - IFPR, Cornélio Procópio, Brazil
  • fYear
    2011
  • fDate
    11-15 Sept. 2011
  • Firstpage
    844
  • Lastpage
    849
  • Abstract
    This paper deals with compensation algorithm schemes used in single-phase Uninterruptiple Power Supply (UPS) system, allowing harmonic suppression and sag/swell compensation of the input voltage. In addition, reactive power compensation and harmonic suppression of the input current are also carried out, resulting in an effective power factor correction. To compensate the input current and the output voltage, Synchronous Reference Frame (SRF) based controllers are used. Although the SRF method is itself based on balanced three-phase loads, it can be adapted for use in single-phase loads. The UPS is composed of two single-phase PWM converters to perform the active power line filter functions. The single-phase UPS can be implemented by adopting two different operation modes. In the first mode the series converter acts as a sinusoidal current source, while the parallel converter acts as a sinusoidal voltage source. In the second mode, the series converter acts as a non-sinusoidal voltage source, while the parallel converter acts as a non-sinusoidal current source. A comparative analysis of the two operation modes is made, in which the advantages and disadvantages of each are discussed. Validation results are presented to confirm the theoretical development and performance of the single-phase UPS system.
  • Keywords
    PWM power convertors; active filters; power factor correction; power harmonic filters; power supply quality; uninterruptible power supplies; voltage regulators; PWM converter; active power line filter function; harmonic suppression; nonsinusoidal current source; power factor correction; reactive power compensation; sag compensation; series parallel filtering capabilities; single phase UPS system; sinusoidal voltage source; swell compensation; synchronous reference frame based controller; uninterruptiple power supply; Harmonic analysis; Phase locked loops; Power harmonic filters; Pulse width modulation converters; Uninterruptible power systems; Voltage control; Voltage measurement; Harmonic suppression; Reactive compensation; SRF-based controller; UPS system;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Conference (COBEP), 2011 Brazilian
  • Conference_Location
    Praiamar
  • ISSN
    2175-8603
  • Print_ISBN
    978-1-4577-1644-7
  • Electronic_ISBN
    2175-8603
  • Type

    conf

  • DOI
    10.1109/COBEP.2011.6085170
  • Filename
    6085170