DocumentCode :
2399776
Title :
Measuring battery plant ripple currents
Author :
Wilson, David B.
fYear :
1992
fDate :
13-14 April 1992
Firstpage :
13
Lastpage :
17
Abstract :
Utility users of uninterruptible power supply (UPS) have become concerned with the premature wear-out of the battery systems. In looking for a cause for accelerated battery wear-out, a study of the electrical environment was made in order to identify the differences between the relatively new UPS applications and the older telecommunications applications. The types of sites from which data were taken are: central office and PBX telecom, single-unit UPS, multiple-unit UPS with individual battery systems, and multiple-unit UPS with a shared battery system. In most instances the load on the DC system was unknown. Several UPS brands were tested to get a representative sample. The author describes the data acquisition system used and data reduction issues and proposes a standard method for data acquisition and a recommended instrument list.<>
Keywords :
battery storage plants; data acquisition; electric current measurement; uninterruptible power supplies; accelerated battery wear-out; battery plant ripple currents; data acquisition system; individual battery systems; multiple-unit UPS; shared battery system; uninterruptible power supply; Application software; Battery charge measurement; Cameras; Current measurement; Manufacturing; Oscilloscopes; Power system reliability; Testing; Uninterruptible power systems; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering Problems in the Rubber and Plastics Industries, 1992., IEEE Conference Record of 1992 Forty-Fourth Annual Conference of
Conference_Location :
Akron, OH, USA
Print_ISBN :
0-7803-0543-4
Type :
conf
DOI :
10.1109/RAPCON.1992.167492
Filename :
167492
Link To Document :
بازگشت