DocumentCode
2422201
Title
Comprehensive diagnostic and aging assessment method of solid insulation in transformer
Author
Dong, M. ; Yan, Z. ; Zhang, G.J.
Author_Institution
Sch. of Electr. Eng., Xi´´an Jiaotong Univ., China
fYear
2003
fDate
19-22 Oct. 2003
Firstpage
137
Lastpage
140
Abstract
Up to now, the diagnostic methods and criteria for operating oil-immersed power transformers are still under research. Besides the investigation of diagnostic methods for solid insulation in transformer, quite a lot of data collected from the in-service transformers under different condition included the data of failed or defected transformers have been analyzed systematically in this paper, such as its furfural concentrations, dissolved gases in oil, the degree of polymerization of insulating paper and pressboard, etc. Statistic analyses or the membership functions had been carried out to reveal the relationship between the contents of furfural or gases in oil and the aging of solid insulation. And the life expectancy of power transformer is studied. Finally a comprehensive diagnostic method is put forward for the aging assessment of solid insulation. The examples of application show the method is effective and easy to apply for the operating transformers.
Keywords
ageing; organic insulating materials; power transformer insulation; comprehensive aging assessment method; comprehensive assessment method; degree of polymerization; dissolved gases; furfural concentrations; in-service transformers; insulating paper; life expectancy; oil-immersed power transformers; pressboard; solid insulation; transformer; Aging; Dissolved gas analysis; Gas insulation; Gases; Oil insulation; Petroleum; Plastic insulation; Power transformer insulation; Power transformers; Solids;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2003. Annual Report. Conference on
Print_ISBN
0-7803-7910-1
Type
conf
DOI
10.1109/CEIDP.2003.1254813
Filename
1254813
Link To Document