DocumentCode
2474150
Title
An analysis of the partial discharge pattern related to the artificial defects introduced at the interface in XLPE cable joint using laboratory model
Author
Lee, J.S. ; Koo, J.Y. ; Lim, Y.S. ; Kim, J.T. ; Lee, S.K.
Author_Institution
EM&C, Hanyang Univ., Kyunggi-Do, South Korea
fYear
2002
fDate
2002
Firstpage
482
Lastpage
485
Abstract
In this work, in order to realize the possible defects at the cable joint interface, four different types of artificial defects are provided such as conducting, insulating substances, void and scratches. The analysis related to the PD patterns has been performed by means of Phase Resolved Partial Discharge Analysis (PRPDA) and Chaotic Analysis of Partial Discharge (CAPD) as well. The results show that it could be pointed out that each defect has shown particular characteristics in its pattern respectively and that the nature of the defect causing partial discharge could be identified more distinctively when the CAPD is combined with a conventional statistical method, PRPDA.
Keywords
XLPE insulation; cable jointing; partial discharges; power cable insulation; XLPE cable joint; artificial defects; chaotic analysis; insulating substances; laboratory model; partial discharge pattern; phase resolved partial discharge analysis; scratches; voids; Cable insulation; Chaotic communication; Partial discharges; Pattern analysis; Performance analysis; Power cable insulation; Power cables; Pulse measurements; Stress; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
Print_ISBN
0-7803-7502-5
Type
conf
DOI
10.1109/CEIDP.2002.1048839
Filename
1048839
Link To Document