• DocumentCode
    25076
  • Title

    Compensation with Hybrid Active Power Filter in an Industrial Plant

  • Author

    Corasaniti, V.F. ; Barbieri, M.B. ; Arnera, P.L.

  • Author_Institution
    Univ. Nac. de La Plata (FI-UNLP), La Plata, Argentina
  • Volume
    11
  • Issue
    1
  • fYear
    2013
  • fDate
    Feb. 2013
  • Firstpage
    447
  • Lastpage
    452
  • Abstract
    This paper presents the application of a hybrid active power filter for reactive and harmonic compensation at the level of Medium Voltage (MV) of an electrical network of an industrial plant. It is considered as control algorithm, the application of the d-q theory and performing the current measuring in the system, establishing a feedback control loop (feedback). It is analyzed a hybrid topology called Shunt Hybrid Active Power Filter SHAPF. This proposal uses an existing capacitor bank, transformed into a passive filter, and connected in series with the Active Filter to build a hybrid filter in which the compensation supplement is made by the active filter. We analyze different scenarios of operation. The topology has very good performance under steady state and transient.
  • Keywords
    industrial plants; power filters; feedback control loop; harmonic compensation; hybrid active power filter; industrial plant; medium voltage; reactive compensation; Active filters; Capacitors; Hybrid power systems; Industrial plants; Power harmonic filters; Pulse width modulation; Topology; Harmonic Distortion; Industrial Plants; Power Active Filters; Reactive compensation;
  • fLanguage
    English
  • Journal_Title
    Latin America Transactions, IEEE (Revista IEEE America Latina)
  • Publisher
    ieee
  • ISSN
    1548-0992
  • Type

    jour

  • DOI
    10.1109/TLA.2013.6502844
  • Filename
    6502844