DocumentCode :
2513756
Title :
Statistical investigation of influence of surge arresters on lightning surge level in 220 V AC power systems
Author :
Wang, Shunchao ; Chen, Shuiming ; Deng, Xuemei ; Hu, Jun
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear :
2010
fDate :
12-16 April 2010
Firstpage :
1255
Lastpage :
1258
Abstract :
Lightning caused surge voltages in low-voltage AC power circuits are studied statistically based on the Monte Carlo method in this paper. The finite difference time domain (FDTD) method is used to solve the multi-conductor transmission line equations. A transformer model is incorporated into the FDTD solution. Both direct and indirect lightning strikes are taken into account in the statistical evaluation. Results show that installing surge arresters on 10 kV overhead lines has a notable influence on the surge level on 220V sides.
Keywords :
Monte Carlo methods; arresters; finite difference time-domain analysis; power transmission protection; AC power systems; FDTD method; Monte Carlo method; finite difference time domain; lightning surge level; low-voltage AC power circuits; method; multiconductor transmission line equations; statistical investigation; surge arresters; transformer model; voltage 10 kV; voltage 220 V; Arresters; Circuits; Finite difference methods; Lightning; Multiconductor transmission lines; Power system modeling; Power systems; Power transmission lines; Surges; Time domain analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility (APEMC), 2010 Asia-Pacific Symposium on