Title :
Investigation of the `non-linear´ dielectric response of water tree-aged XLPE cables in the time and frequency domain
Author :
Kuschel, M. ; Kryszak, B. ; Kalkner, W.
Author_Institution :
Tech. Univ. Berlin, Germany
Abstract :
Heavily water tree-aged cables show a so-called `non-linear´ dielectric response with respect to the voltage whose origin is still unknown and which is difficult to relate to the actual condition of the cable insulation. However, the `non-linear´ behaviour is one possible diagnostic criterion. The aim of the work presented in this paper is to investigate this `non-linear´ dielectric response in the time and frequency domain, as well as to correlate both domains by different mathematical approaches. The `non-linear´ behaviour of the dielectric response is found to be different in the time and frequency domain. Also a transition from `non-linear´ to `linear´ behaviour of the dielectric response can be observed in some cases above a certain voltage
Keywords :
XLPE insulation; ageing; frequency-domain analysis; insulation testing; power cable insulation; power cable testing; time-domain analysis; trees (electrical); XLPE cable insulation; diagnosis; frequency domain; nonlinear dielectric response; time domain; water tree ageing; Aging; Cable insulation; Current measurement; Dielectric measurements; Dielectrics and electrical insulation; Frequency domain analysis; Medium voltage; System testing; Trees - insulation; Voltage measurement;
Conference_Titel :
Conduction and Breakdown in Solid Dielectrics, 1998. ICSD '98. Proceedings of the 1998 IEEE 6th International Conference on
Conference_Location :
Vasteras
Print_ISBN :
0-7803-4237-2
DOI :
10.1109/ICSD.1998.709232