Title :
Designing safe and reliable grounding in AC substations with poor soil resistivity: An interpretation of IEEE STD. 80
Author :
Ackerman, Andrew ; Sen, P.K. ; Oertli, Clifton
Author_Institution :
NEI Electr. Power Eng., Inc., Arvada, CO, USA
Abstract :
IEEE Std. 80 “IEEE Guide for Safety in AC Substation Grounding” is most commonly used in the design of substation ground grids and is the basis for today´s commercially available software. This paper discusses alternate design approach for substation grounding in areas that have high soil resistivity. It discusses various methods for designing a substation grounding system without changing the characteristics of the soil with additives or adding ground wells to establish a low resistance to remote earth. An interpretation of the equations and a better understanding of the IEEE Std. 80 allows the engineer to provide a cost effective, safe and reliable grounding system design when poor soil conditions exist.
Keywords :
IEEE standards; earthing; reliability; soil; substations; AC substations; IEEE Std. 80; additives; ground wells; reliable grounding designing; remote earth; safe grounding designing; soil resistivity; substation ground grid design; Grid Resistance; Ground Grid Design; Ground Potential Rise; Ground Rod; Resistivity; Split Factor; Step Potential; Touch Potential;
Conference_Titel :
Petroleum and Chemical Industry Technical Conference (PCIC), 2012 Record of Conference Papers Industry Applications Society 59th Annual IEEE
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4673-0924-0
DOI :
10.1109/PCICON.2012.6549644