DocumentCode :
2568037
Title :
VRLA batteries in photovoltaic energy storage systems for telecom applications
Author :
Frank, R. ; Giess, H.
Author_Institution :
Accumulatoren Fabrik Oerlikon, Zurich, Switzerland
Volume :
1
fYear :
1993
fDate :
27-30 Sep 1993
Firstpage :
54
Abstract :
The Swiss PTT has installed an active repeater station powered by a photovoltaic energy storage system (PVES) on the peak Pit Muttler situated in the vicinity of the border corner Switzerland-Austria-Italy at an altitude of 3294 m. The PVES system consists of 72 60 W (4.32 kW-36m2) solar panels with associated maximum power trackers and charging controllers. The photovoltaic energy is stored in 24 V batteries using 2 V VRLA Compact Power cells with a nominal capacity of 1000 Ah (C10) per cell. In order to evaluate the worst case conditions of extremely low temperatures within the battery room, the low temperature (-30°C) and the low voltage (0.00 V/cell) behaviour of such cells is reported. Batteries survive freeze/thaw cycles unscathed and can be recharged with the electrolyte “frozen”
Keywords :
lead; photovoltaic power systems; repeaters; secondary cells; solar cell arrays; telecommunication power supplies; 2 V; 24 V; 3294 m; 4.32 kW; 60 W; Pb; Pit Muttler peak; Switzerland; VRLA Compact Power cells; active repeater station; battery recharging; charging controllers; freeze/thaw cycles; frozen electrolyte; low temperature behaviour; low voltage behaviour; maximum power trackers; photovoltaic energy storage system; photovoltaic energy storage systems; solar panels; valve regulated Pb-acid battery; Batteries; Energy storage; Gold; Photovoltaic systems; Solar power generation; Telecommunications; Temperature;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, INTELEC '93. 15th International
Conference_Location :
Paris
Print_ISBN :
0-7803-1842-0
Type :
conf
DOI :
10.1109/INTLEC.1993.388469
Filename :
388469
Link To Document :
بازگشت