DocumentCode
25794
Title
High-Resistance Grounded Power-System Equivalent Circuit Damage at the Line–Ground Fault Location—Part II
Author
Paul, Deleglise ; Sutherland, Peter E.
Author_Institution
AECOM Technol. Corp., Oakland, CA, USA
Volume
50
Issue
6
fYear
2014
fDate
Nov.-Dec. 2014
Firstpage
4188
Lastpage
4196
Abstract
This paper provides the electrical equivalent circuits of high-resistance grounded (HRG) power systems other than the delta-wye-connected utility power supply transformer included in Part I of this paper. This paper also provides the HRG of a medium-voltage generator for connection to an industrial power system and to a utility power system, and this paper discusses a line-ground fault with fault resistance. Three-line diagrams of ungrounded power systems are also included to illustrate the HRG application and its effect on the ground fault current during the line-ground fault. The damage at the fault location is based on the assumption that the fault remains a line-ground fault until it is cleared by appropriate ground fault protection relays. The fault resistance and the fault current that have an effect on the damage at the fault location are included. This paper provides guidance to update the current edition of the IEEE STD. 142, with respect to HRG systems.
Keywords
earthing; equivalent circuits; fault location; power system faults; power transformers; relay protection; IEEE STD. 142; electrical equivalent circuits; equivalent circuit damage; fault resistance; ground fault current; ground fault protection relays; high resistance grounded power system; industrial power system; line ground fault location; medium voltage generator; power supply transformer; three-line diagrams; utility power system; Circuit faults; Fault currents; Generators; Grounding; Relays; Resistance; Arcing fault; fault resistance; ground fault protection relay; high-resistance grounded (HRG) system; system charging current;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2014.2346691
Filename
6877709
Link To Document