• DocumentCode
    2586256
  • Title

    Corona caused deterioration of ADSS fiber-optic cables on high voltage lines

  • Author

    Karady, George G. ; Besztercey, Gyula ; Tuominen, Monty W.

  • Author_Institution
    Dept. of Electr. Eng., Arizona State Univ., Tempe, AZ, USA
  • Volume
    2
  • fYear
    1999
  • fDate
    31 Jan-4 Feb 1999
  • Abstract
    Summary form only as given. Deterioration of ADSS (all-dielectric self-supporting) fiber optic cable jacket material has been reported near the tips of armor rod assemblies installed on high-voltage transmission lines. Field observations and laboratory tests revealed that corona can exist on the tips of the armor rod. Electric field analysis reported herein reveals that the tip surface gradients are high enough to produce corona. Field conditions have been duplicated in a high voltage test chamber and jacket damage has been observed near generated corona. The deterioration mechanism is identified and jacket life expectancy is estimated. Different mitigation techniques are suggested.
  • Keywords
    cable testing; corona; electric fields; optical cables; power transmission lines; ADSS fiber-optic cables; all-dielectric self-supporting optical cables; corona deterioration studies; corona production; deterioration mechanism; electric field analysis; field observations; high-voltage power transmission lines; high-voltage test chamber; jacket damage; laboratory tests; life expectancy; mitigation techniques; tip surface gradients; Assembly; Corona; Laboratories; Life estimation; Optical fiber cables; Optical fiber testing; Optical fibers; Optical materials; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society 1999 Winter Meeting, IEEE
  • Print_ISBN
    0-7803-4893-1
  • Type

    conf

  • DOI
    10.1109/PESW.1999.747383
  • Filename
    747383