Abstract
A sample risk analysis has been carried out for a typical German urban utility in a 10-kV network group fed by one substation (firm capacity 40 MVA). The new approach of risk analysis in electrical networks combines one of the results of reliability studies (components contribution to expected-energy-not-supplied-EENS) with the input data (components failure rate and repair time) and enables an assessment of the risk caused by component failures. With this approach reinvestment and maintenance strategies can be improved significantly
Keywords
distribution networks; power distribution reliability; power transmission reliability; risk analysis; transmission networks; 10 kV; German urban utility; component failure; distribution network; maintenance strategy; reinvestment strategy; reliability study; risk analysis; risk assessment; substation; transmission network; Capacity planning; Costs; Intelligent networks; Maintenance; Power cables; Power system analysis computing; Power system reliability; Risk analysis; Routing; Substations; Cable Replacement Strategy; Reliability Centered Maintenance; Risk Analysis;