DocumentCode
2596567
Title
Voltage harmonic distortion measurement issue in smart-grid distribution system
Author
Luszcz, Jaroslaw ; Smolenski, Robert
Author_Institution
Fac. of Electr. & Control Eng., Gdansk Univ. of Technol., Gdansk, Poland
fYear
2012
fDate
21-24 May 2012
Firstpage
841
Lastpage
844
Abstract
This paper presents the investigation results of voltage harmonic transfer accuracy problems through voltage transformers which are widely used in power quality monitoring systems in medium and high voltage grids. A simplified lumped parameters circuit model of the voltage transformer is presented and verified by simulation and experimental investigations. A number voltage transformers typically used in medium voltage grid has been tested in the conducted electromagnetic interference frequency range up to 30 MHz. The obtained results confirm that broadband voltage transfer function of the voltage transformer usually exhibits various irregularities which are primarily associated with voltage transformer winding parasitic capacitances.
Keywords
electromagnetic interference; harmonic distortion; potential transformers; power distribution; power supply quality; power system harmonics; smart power grids; voltage measurement; broadband voltage transfer function; electromagnetic interference frequency; high-voltage grid; medium-voltage grid; power quality monitoring systems; simplified lumped parameter circuit model; smart-grid distribution system; voltage harmonic distortion measurement; voltage harmonic transfer accuracy; voltage transformer winding parasitic capacitance; Frequency measurement; Harmonic analysis; Integrated circuit modeling; Power system harmonics; Voltage measurement; Voltage transformers; Windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility (APEMC), 2012 Asia-Pacific Symposium on
Conference_Location
Singapore
Print_ISBN
978-1-4577-1557-0
Electronic_ISBN
978-1-4577-1558-7
Type
conf
DOI
10.1109/APEMC.2012.6238024
Filename
6238024
Link To Document