Transformer and Bus Backup Protection Based on Longitudinal Comparison Principle
Author :
Pan, Z.C. ; Ding, L. ; Wang, R. ; Cong, W.
Author_Institution :
Sch. of Electr. Eng., Shandong Univ., Jinan
fYear :
2005
fDate :
2005
Firstpage :
1
Lastpage :
4
Abstract :
A new transformer backup protection based on longitudinal comparison principle (LCP) is introduced in this paper. The fault can be located by comparing action of measurement elements on all sides of transformer simultaneously. If the transformer internal faults occur, backup protection trips the breakers of all sides with a short time delay to avoid nuisance tripping caused by inrush current. If an external fault occurs, the backup protection can determine the fault side and trip the corresponding breaker after a predetermined time coordinated with downstream relays. The coordination of operation time and reach among overcurrent relays on different side is not needed. The backup protection can provide good protection performance for transformer and adjacent buses. It can shorten the operation time and improve selectivity and sensitivity
Keywords :
fault location; overcurrent protection; power transformer protection; relay protection; LCP; breaker; downstream relays; fault location; inrush current; longitudinal comparison principle; measurement elements; operation time coordination; overcurrent relays; sensitivity; time delay; transformer-bus backup protection; Circuit faults; Current transformers; Delay effects; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Substation protection; Surge protection; Backup protection; Longitudinal comparison principle; Measure elements; Transformer and Bus;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition: Asia and Pacific, 2005 IEEE/PES
Conference_Location :
Dalian
Print_ISBN :
0-7803-9114-4
Type :
conf
DOI :
10.1109/TDC.2005.1547042
Filename :
1547042
Link To Document :
بازگشت