DocumentCode :
2629822
Title :
A new stationary on-line PD monitoring system for power transformers
Author :
Li, F.Q. ; Jiang, L. ; Zhu, D.H. ; Tan, K.X. ; Wang, C.C. ; Jin, X.H. ; Cheng, T.C.
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume :
2
fYear :
2000
fDate :
2000
Firstpage :
686
Abstract :
This on-line PD monitoring system can monitor partial discharge in two three-phase transformers continuously. It has the functions with fault reminiscence, fault warning and fault location. By means of using wide-band, multi-channel, high sampling rate and large capacity data acquisition system makes system has a good basis, it can use various kinds of digital signal processing method. Furthermore various kinds of data processing method can be added into the system flexibly by taking the Component Object Model as the basis of the whole software. This system has good expansibility and flexibility and can fit the requisition for different equipment and monitoring parameters
Keywords :
computerised monitoring; distributed object management; insulation testing; partial discharge measurement; power transformer insulation; power transformer testing; component object model; data acquisition system; data processing; digital signal processing; fault location; fault reminiscence; fault warning; sampling rate; stationary on-line partial discharge monitoring system; three-phase power transformer; Data processing; Grounding; Hardware; Monitoring; Partial discharges; Power engineering computing; Power transformers; Signal processing; Signal sampling; Wideband;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2000 Annual Report Conference on
Conference_Location :
Victoria, BC
Print_ISBN :
0-7803-6413-9
Type :
conf
DOI :
10.1109/CEIDP.2000.884051
Filename :
884051
Link To Document :
بازگشت