Title :
Methods of shielding primary windings on high voltage instrument transformers
Author :
Wallace, David ; Grzybowski, Stanislaw
Author_Institution :
ABB Inc., Crystal Springs, MS, USA
Abstract :
One of the main problems encountered in the design and construction of high voltage potential transformers is achieving the ability to withstand high voltage transients. These transients can be the result of lightening, switching surges, equipment failure and flash-overs. Issues that arise from these transients tend to occur in the outermost layers of the primary coil, resulting in damage, such as layer to layer insulation puncture and creepage failure. A common technique used in averting this, involves the utilization of a line shield, over the last layer of the primary winding. This paper will discuss the methodology involved in proper line shielding, using the design for a 115 kV class voltage transformer, as an example.
Keywords :
coils; potential transformers; transformer windings; transients; high voltage instrument transformer damage; high voltage potential transformer design; high voltage transients; primary coil; primary winding shielding; Copper; Instruments; Insulation;
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2014 International Conference on
Conference_Location :
Poznan
DOI :
10.1109/ICHVE.2014.7035435