DocumentCode :
2635438
Title :
CCVT calibration for harmonic voltage measurement by digital simulation and field test
Author :
Liang, Shun ; Hu, Qiaohui ; Lee, Wei-Jen
Author_Institution :
Energy Syst. Res. Center (ESRC), Univ. of Texas at Arlington (UTA), Arlington, TX, USA
fYear :
2009
fDate :
4-6 Oct. 2009
Firstpage :
1
Lastpage :
5
Abstract :
This paper reports a CCVT calibration effort for harmonic voltage measurement purpose. A set of frequency response studies are conducted on two types of 345-kV Coupling Capacitor Voltage Transformers (CCVT). The Electro-Magnetic Transients Program (EMTP) is used to develop the CCVT model and conduct this digital simulation. The accuracy of the CCVT frequency response study result is verified through comparison of the EMTP digital simulation results with those obtained from field measurements. The comparison results demonstrate that the developed model can accurately predict CCVT frequency response, and can provide good adjustment values for harmonic measurement purpose.
Keywords :
Calibration; Capacitors; Digital simulation; EMTP; Frequency measurement; Frequency response; Predictive models; Testing; Voltage measurement; Voltage transformers; CCVT Frequency Response; CCVT Modeling; EMTP Simulation; Harmonic Measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
North American Power Symposium (NAPS), 2009
Conference_Location :
Starkville, MS, USA
Print_ISBN :
978-1-4244-4428-1
Electronic_ISBN :
978-1-4244-4429-8
Type :
conf
DOI :
10.1109/NAPS.2009.5484067
Filename :
5484067
Link To Document :
بازگشت