• DocumentCode
    2636629
  • Title

    Preventive inspection of line insulators through corona emission: A case study

  • Author

    Vasquez-Arnez, R.L. ; Jardini, M.G.M. ; Masuda, M. ; Carita, L.A., Jr. ; Jardini, J.A.

  • Author_Institution
    Contrel Eng. Ltd., São Paulo, Brazil
  • fYear
    2010
  • fDate
    19-22 April 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents the main results regarding the presence of corona on 138 kV lines. Although the study and analysis was mainly focused on the obtention of corona activity through a UV camera, results stemming from an IR camera will also be presented. The substitution of suspected flawed insulators represent to most of the distribution utilities one of the causes of major concern. The results performed in both a HV laboratory and field tests are presented herein. It was not found a similar behaviour and intensity of the corona activity between both cases. However, both type of tests agreed in that the faulty insulator(s) that have its leakage current increased, does not show corona activity.
  • Keywords
    Birds; Cameras; Corona; Foot; Inspection; Insulation; Maintenance; Power system reliability; Power transmission lines; Vehicles; 138 kV line; Corona activity; Flawed Insulators; Preventive Inspection; UV & IR camera;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2010 IEEE PES
  • Conference_Location
    New Orleans, LA, USA
  • Print_ISBN
    978-1-4244-6546-0
  • Type

    conf

  • DOI
    10.1109/TDC.2010.5484226
  • Filename
    5484226