Title :
System impacts evaluation of a single-phase traction load on a 115 W transmission system
Author :
Sutherland, Peter ; McGranaghan, Mark ; Waclawiak, Marek
Abstract :
Summary form only given. The system impact of a new transit substation may include harmonic distortion, voltage unbalance and flicker. Measurements were taken at a similar substation, and system simulations were performed for the planned substation. It was found that the Metro North train load produced significant levels of third harmonic current. Resonances in the 115 kV system were simulated and found to be at frequencies which are not critical. A third harmonic filter is needed in order to meet IEEE 519 requirements. Unbalance and flicker were found to be negligible
Keywords :
harmonic distortion; power harmonic filters; substations; traction; transmission networks; 115 kV; IEEE 519 requirements; Metro North train load; harmonic current; harmonic distortion; single-phase traction load; system impacts evaluation; third harmonic filter; transit substation; transmission system; voltage flicker; voltage unbalance; Distortion measurement; Frequency; Harmonic distortion; Harmonic filters; Performance evaluation; Power harmonic filters; Resonance; Substations; Voltage fluctuations;