  • Title

    The effects of voltage waveform factors on cable life estimation using measured distorted voltages

  • Author

    Mazzanti, Giovanni ; Passarelli, Gaetano ; Russo, Angela ; Verde, Paola

  • Author_Institution
    Dept. of Electr. Eng., Bologna Univ.
  • fYear
    0
  • fDate
    0-0 0
  • Abstract
    This work investigates expected life reduction of power cables under harmonic pollution, by processing the results of voltage harmonics measurements. Life estimates come from a life model developed by the authors in former studies, used here in its complete form, with all voltage waveform factors, i.e. peak, shape and rms factor. The application regards MV XLPE-insulated cables. The whole day duty cycle is split into rush hours and non-rush hours, each characterized by a different level of harmonic distortion. The results show that life is significantly reduced with respect to rated sinusoidal life, and that both shape and peak factors play a major role, shape factor during rush hours, peak factor during non-rush hours
  • Keywords
    XLPE insulation; harmonic distortion; power cable insulation; remaining life assessment; XLPE-insulated cables; distorted voltage harmonics measurement; expected life reduction; harmonic distortion; harmonic pollution; power cable life estimation; voltage waveform factors; Costs; Distortion measurement; Harmonic distortion; Life estimation; Pollution measurement; Power cables; Power system harmonics; Shape; Thermal stresses; Voltage; cables; harmonic distortion; life estimation; power system harmonics; reliability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2006. IEEE
  • Conference_Location
    Montreal, Que.
  • Print_ISBN
    1-4244-0493-2
  • Type

    conf

  • DOI
    10.1109/PES.2006.1709033
  • Filename
    1709033