DocumentCode :
267582
Title :
Novel impedance determination method for phase-to-phase loops
Author :
Dzienis, Cezary ; Yelgin, Yilmaz ; Steynberg, Gustav ; Claus, Michael
Author_Institution :
R&D, Siemens AGIC SG EA PRO D, Berlin, Germany
fYear :
2014
fDate :
18-22 Aug. 2014
Firstpage :
1
Lastpage :
7
Abstract :
In this paper a novel impedance determination method for the phase-to-phase loops is described. This approach promises a better accuracy of the reactance calculation of the faulty loops. Thus, better selectivity and security in operation of the distance element applied for the protection of transmission and distribution lines is guaranteed. Moreover, with this new method the separation of the fault resistance from load condition is achieved. Due to this fact, special measures for load encroachment are not necessary. It contributes to simplification of distance protection settings.
Keywords :
power distribution faults; power distribution protection; power transmission faults; power transmission protection; distance protection settings; distribution line protection; fault resistance; faulty loops; impedance determination method; load condition; phase-to-phase loops; reactance calculation; transmission line protection; Circuit faults; Electrical resistance measurement; Impedance; Impedance measurement; Load flow; Radio frequency; Resistance; distance element; impedance determination; line protection; reactance method; transition resistance separation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Systems Computation Conference (PSCC), 2014
Conference_Location :
Wroclaw
Type :
conf
DOI :
10.1109/PSCC.2014.7038393
Filename :
7038393
Link To Document :
بازگشت