A new lossless circuit balancing the MV distribution systems from insulated shield wires of HV lines
Author
Cinieri, E.
Author_Institution
Dept. of Electr. Eng., l´´Aquila Univ., Italy
Volume
2
fYear
1999
fDate
11-16 Apr 1999
Firstpage
722
Abstract
Three-phase scheme shield wire lines (MV lines obtained by isolating 2 shield wires of an HV transmission line) are intrinsically unbalanced. Even though the load supplied is balanced, negative sequence components of the voltage are originated by this asymmetry. Balancing means are necessary in order to contain these components to tolerable values. The paper presents a new balancing circuit, made of static, lossless, low cost components. The circuit has important advantages with respect to the compensating means proposed and applied in the past. In particular its application, in addition to the balancing effect, enables reduction of the voltage drop and does not cause any increase of the active power losses. The paper presents the circuit in two different forms together with the principles that justify its genesis
Keywords
compensation; distribution networks; equivalent circuits; power distribution lines; MV distribution systems; active power losses; insulated shield wires; lossless balancing circuit; three-phase scheme shield wire lines; voltage drop reduction; voltage negative sequence components; Cable insulation; Conductors; Costs; Dielectrics and electrical insulation; Equivalent circuits; Impedance; Power transformer insulation; Power transmission lines; Voltage; Wires;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1999 IEEE
Conference_Location
New Orleans, LA
Print_ISBN
0-7803-5515-6
Type
conf
DOI
10.1109/TDC.1999.756139
Filename
756139
Link To Document