Abstract
This paper analyzes the phenomenon of sympathetic interaction between transformers which is very likely to occur when a transformer is energized on to a system where are other transformers already connected. This interaction significantly changes the duration and the magnitude of the transient magnetizing currents in the transformers involved and may lead to maloperation of some power protections. This article presents the formation process of sympathetic inrush current through the flux analytical expression and bias flux attenuation between two parallel operation transformers. After that, the reasons of sympathetic inrush current generation are illustrated. Presented analytical analysis is valuable for comprehensive understanding of sympathetic inrush current, estimating the reasons of generation and eliminating it.
Keywords
magnetic flux; magnetisation; power transformer protection; transient analysis; flux analytical expression; flux attenuation; parallel operation transformers; power protections; sympathetic inrush current generation; transient magnetizing currents; Circuit faults; Magnetic flux; Power transformers; Resistance; Surge protection; Surges; Transient analysis; Inrush Current; Power Protections; Transformer Saturation; Transient Phenomenon;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Power Engineering (EPE), Proccedings of the 2014 15th International Scientific Conference on
Conference_Location
Brno
Type
conf
DOI
10.1109/EPE.2014.6839519
Filename
6839519
Link To Document