Investigation of circulating ground currents occurring during UPS/generator paralleling
Author
Brown, William A. ; Kennedy, James M. ; Linkhart, Charles
Author_Institution
Schneider Electr., Nashville, TN, USA
fYear
2010
fDate
9-13 May 2010
Firstpage
1
Lastpage
9
Abstract
The paralleling of uninterruptible power supplies (UPS´s) with generators during UPS bypass operations can result in high-magnitude circulating ground currents under certain conditions. This paper explores the phenomena that cause this system behavior, presents data from an actual documented occurrence, and discusses methods to reduce or eliminate such circulating currents.
Keywords
Circuit breakers; Coils; Control systems; Maintenance; Power generation; Rectifiers; Stator windings; Switches; Uninterruptible power systems; Voltage; AC generators; grounding; uninterruptible power systems;