Abstract :
Ideally, it is desirable to design and manufacture a transformer winding that can render all its internal resonances non-excitable. This study examines the effectiveness of an interleaved winding in achieving this goal. While investigating its effectiveness, it led to the establishment of a much desired theoretical basis that reinforces the reasons put forward in the literature to explain internal insulation failures observed in interleaved windings used in extra high voltage (EHV) transformers. Numerical calculations along with experimental verification on actual transformer windings are presented. This study reveals that most of the natural frequencies that are normally non-excitable in the line and neutral current responses of an interleaved winding have been rendered excitable in the disk-to-disk voltages, thus, providing favourable conditions for insulation overstress because of resonant overvoltages. Prevalence of such a condition is an inherent characteristic of interleaved windings.
Keywords :
high-voltage techniques; interference suppression; neutral currents; overvoltage; resonance; transformer insulation; transformer windings; EHV transformer; disk-to-disk voltages; experimental verification; insulation failure; insulation overstress; interleaved winding; natural frequency suppression; neutral current response; resonance; resonant overvoltage; transformer winding;
fLanguage :
English
Journal_Title :
Electric Power Applications, IET
Publisher :
iet
ISSN :
1751-8660
Type :
jour
DOI :
10.1049/iet-epa.2012.0362
Filename :
6553655
Link To Document :
بازگشت