• DocumentCode
    273161
  • Title

    Condition monitoring of 132 kV bushings

  • Author

    Domun, M.K.

  • Author_Institution
    Electr. Council Res. Centre, Capenhurst, UK
  • fYear
    1988
  • fDate
    27-30 Jun 1988
  • Firstpage
    199
  • Lastpage
    203
  • Abstract
    Interest in diagnostic monitoring of HV plant has increased dramatically as a result of the ever increasing proportion of plant reaching its design life and beyond. This paper provides results of three different sets of diagnostic tests carried out on six 132 kV cable sealing ends and twelve 132 kV oil circuit breaker (OCB) bushings. The techniques include HV DC overvoltage test, HV AC partial discharge (PD) test, HV AC and mV AC capacitance and loss angle measurements, mV DC insulation resistance (IR) test, dissolved gas analysis (DGA) and moisture measurements
  • Keywords
    bushings; capacitance measurement; high-voltage techniques; insulation testing; loss-angle measurement; moisture measurement; overvoltage; partial discharges; power cables; 132 kV; HV AC partial discharge; HV DC overvoltage test; bushings; cable sealing ends; diagnostic monitoring; diagnostic tests; dissolved gas analysis; loss angle measurements; mV AC capacitance; mV DC insulation resistance test; moisture measurements; oil circuit breaker bushing;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Dielectric Materials, Measurements and Applications, 1988., Fifth International Conference on
  • Conference_Location
    Canterbury
  • Print_ISBN
    0-85296-359-9
  • Type

    conf

  • Filename
    9458