• DocumentCode
    273457
  • Title

    The development of an integrated protection and reclosing relay for rural feeders

  • Author

    Rosen, P.R.

  • fYear
    1989
  • fDate
    11-13 Apr 1989
  • Firstpage
    276
  • Lastpage
    280
  • Abstract
    The problems encountered in South African 11 kV rural power lines due to the nature of African electric storms is discussed by the author. The relay developed to overcome the problems (type GAD) offers two overcurrent inputs each of which incorporates low set and high set instantaneous elements for instantaneous tripping as well as IDMTL tripping, switch selectable to normal inverse, very inverse, extremely inverse and definite time lag. A separate earth fault input offers similar features to the overcurrent inputs. In addition, a sensitive earth fault element is provided. The author describes the features of this reclosing relay including: definite time on instantaneous elements; line check, status input sensitive earth fault, and busbar zone protection
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power Protection, 1989., Fourth International Conference on
  • Conference_Location
    Edinburgh
  • Type

    conf