• DocumentCode
    2744563
  • Title

    The establishment of a reference system at VSL for on-site calibration of HV revenue metering systems

  • Author

    Rietveld, Gert ; Diouf, Fatou ; Guo, Xiaodong ; So, Eddy

  • Author_Institution
    VSL, Delft, Netherlands
  • fYear
    2012
  • fDate
    1-6 July 2012
  • Firstpage
    130
  • Lastpage
    131
  • Abstract
    The development of a reference system for on-site calibration of revenue metering systems in high voltage grids is described. The system consists of a three-phase power meter and high-accuracy current and voltage transformers (CTs and VTs). Measurements can be made up to 150 kV (system voltage) and line currents up to 5000 A. The initial characterization of the power meter and the CTs give excellent results, indicating that an overall system uncertainty of 200 μW/VA can be achieved.
  • Keywords
    calibration; current transformers; metering; potential transformers; power grids; power meters; CT; HV revenue metering systems; VSL; VT; high voltage grids; high-accuracy current transformers; on-site calibration; reference system establishment; three-phase power meter; voltage transformers; Accuracy; Calibration; Current measurement; Power measurement; Substations; Voltage measurement; Voltage transformers; billing; current transformer; high current; high voltage (HV); power; power meter; precision measurements; revenue metering; substation; voltage transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements (CPEM), 2012 Conference on
  • Conference_Location
    Washington, DC
  • ISSN
    0589-1485
  • Print_ISBN
    978-1-4673-0439-9
  • Type

    conf

  • DOI
    10.1109/CPEM.2012.6250695
  • Filename
    6250695