Abstract
The system described enables efficient reduction of the line unbalance due to a three phase AC/AC converter feeding an unbalanced load. The cancellation of the inverse component of the line currents fundamentals is chosen as a balancing criterion. It induces a perfect power flow balancing among the three lines because power only deals with fundamentals quantities. Just a little unbalance remains about the other harmonics involving a very small difference between the RMS values of the line currents. The process is rather universal and enables these advantages to be obtained for other power electronics unbalanced circuits
Keywords
power convertors; power systems; thyristor applications; line unbalance; power electronics; power flow balancing; three phase AC/AC converter; thyristor converter loading; unbalanced circuits; unbalanced load; waveform distortion;