• DocumentCode
    276284
  • Title

    On experience in development, designing and construction of AC high and ultra high-voltage and higher actual power transmissions

  • Author

    Nossov, I.M.

  • fYear
    1991
  • fDate
    17-20 Sep 1991
  • Firstpage
    232
  • Lastpage
    234
  • Abstract
    Power transmission characteristics can be drastically improved by application of the development made at the Leningrad State Technical University. It consists of phase splitting into a greater number of constituent wires, accompanied by optimization of their relative position in space (both at the support and in the span). In this case, the electric intensity on the surface of all wires of all phases should be close to the maximum permissible value to limit corona discharge. Under these conditions, the actual power of the line increases proportionally with the number of wire splittings and diameter. The wave and inductive impedance of the line decreases correspondingly. The author discusses the application of the method to three power lines: Leningrad-Moscow 750 kV line; the Pskov SDEPS-Novasokolniki 330 kV line; and the Boguchan SDEPS-Kansk Station 500 kV line
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    AC and DC Power Transmission, 1991., International Conference on
  • Conference_Location
    London
  • Print_ISBN
    0-85296-517-6
  • Type

    conf