DocumentCode :
278231
Title :
Harmonic current cancellation techniques
Author :
Pedder, D.A.G.
Author_Institution :
ERA Technol., Leatherhead, UK
fYear :
1991
fDate :
33324
Firstpage :
42552
Lastpage :
42559
Abstract :
The reduction of supply current distortion by harmonic cancellation is examined. The technique to be described involves the use of four-quadrant controlled-current sources/sinks as parallel-connected current-waveform correctors. The add-on units are arranged to inject harmonic currents into the supply as demanded by the distorting loads so that the supply current may be near-sinusoidal and in-phase with the supply voltage. If current injection is correctly carried out and in close proximity to the distorting load, EMC problems associated with common impedances and radiation from wiring will be minimised and wiring and plant requirements may be reduced
Keywords :
electromagnetic compatibility; harmonics; EMC; current injection; distorting loads; four-quadrant current sources; harmonic current cancellation; parallel-connected current-waveform correctors; supply current distortion;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Single-Phase Supplies: Harmonic Regulations and Remedies, IEE Colloquium on
Conference_Location :
London
Type :
conf
Filename :
181395
Link To Document :
بازگشت